  1/32 din digital panel meter k3gn k-7 panel indicators 1/32 din digital panel meter k3gn compact and intelligent digital panel meter  a single panel meter covering a wide range of applications. 3 main applicable functions:  process meter (dc voltage/current input).  rpm processor/tachometer (frequency input).  digital data display for pc/plc (rs-485 communications).  easy configuration  multi-range analog input: applicable for all standard analog signals. 6 input ranges available: 4 to 20 ma/0 to 20 ma, 1 to 5 vdc/ 0 to 5 vdc, 5 vdc, 10 vdc.  5 khz max. input-pulse frequency range.  scaling in a wide range of engineering units.  programmable output operation action, decimal point position setting, teaching functi on for input range, leading zero suppression, average processing.  advanced and compact design  very compact 1/32 din housing: 48 (w) x 24 (h) x 83 (d).  5-digit display with programmable display color in red or green.  good visibility: high contrast backlit lcd display.  high protection against water and dust: nema4x/ip66 front panel.  selectable outputs: 2 relay outputs, 3 transistor outputs, rs-485, and combinations of these.  high accuracy: 0.1% full scale.  easy to configure through the front panel or via rs-485.  en/iec conformity with ce marking and ul/csa approval. ? model number structure model number legend 1. input type nd: dc voltage/current, npn pd: dc voltage/current, pnp 2. output type c: 2 relay contact outputs (spst-no) t1: 3 transistor outputs (npn open collector) t2: 3 transistor outputs (pnp open collector) 3. communications output type none: communications not supported flk: rs-485 24 vdc 12 3 k3gn - -
k-8 1/32 din digital panel meter k3gn ordering information list of models specifications ratings note: a control power supply capacity greater than the rated capacity is required when the digital panel meter is turned on. do not f orget to take this into consideration when using severa l digital panel meters. when power is suppl ied, all indicators will light and outputs will be off. when using startup compensation time operation, the display will read ? 00000 ? and all outputs will be off. input type supply voltage output communications no communications rs-485 dc voltage/current, npn 24 vdc dual relays (spst-no) k3gn-ndc 24 vdc k3gn-ndc-flk 24 vdc three npn open collector k3gn-ndt1 24 vdc k3gn-ndt1-flk 24 vdc dc voltage/current, pnp dual relays (spst-no) k3gn-pdc 24 vdc k3gn-pdc-flk 24 vdc three pnp open collector k3gn-pdt2 24 vdc k3gn-pdt2-flk 24 vdc supply voltage 24 vdc operating voltage range 85% to 110% of the rated supply voltage power consumption (see note) 2.5 w max. (at max. dc load with all indicators lit) insulation resistance 20 m ? min. (at 500 vdc) between external terminal and case. insulation provided between inputs, outputs, and power supply. dielectric strength 1,000 vac for 1 min between external terminal and case. insulation provided between inputs, outputs, and power supply. noise immunity 480 v on power supply terminals in normal mode, 1,500 v in common mode, 1 s, or 100 ns for square- wave noise with 1 ns vibration resistance malfunction: 10 to 55 hz, 10 min each in x, y, and z directions; acceleration: 9.8 m/s 2 destruction: 10 to 55 hz, 30 min each in x, y, and z directions; acceleration: 19.6 m/s 2 shock resistance malfunction: models with transistor outputs: 196 m/s 2 for 3 times each in x, y, and z directions models with relay contact outputs: 98 m/s 2 for 3 times each in x, y, and z directions destruction: 294 m/s 2 for 3 times each in x, y, and z directions ambient temperature operating: ? 10 c to 55 c (with no condensation or icing) storage: ? 25 c to 65 c (with no condensation or icing) ambient humidity operating: 25% to 85% (with no condensation) emc (emi) en61326+a1 industry emission enclosure: cispr 11 gr oup 1 class a: cisrp16-1/-2 emission ac mains: cispr 11 gr oup 1 class a: cisrp16-1/-2 (ems) en61326+a1 industry immunity esd: en61000-4-2: 4 kv contact discharge (level 2) 8 kv air discharge (level 3) immunity rf-interference: en61000- 4-3: 10 v/m (amplitude-modulated, 80 mhz to 1 ghz) (level 3) immunity fast transient noise: en61000- 4-4: 2 kv (power line) (level 3) immunity burst noise: 1 kv line to line (i/o signal line) immunity surge: en61000-4-5: 1 kv line to line 2 kv line to ground (power line) immunity conducted disturbance en61000-4- 6: 3 v (0.15 to 80 mhz) (level 2) immunity voltage dip/interrupting en61000-4-11: 0.5 cycles, 0, 180 , 100% (rated voltage) approved standards ul508, csa22.2; conforms to en61326+a1, en61010-1 (iec61010-1) conforms to vde0106/p100 (finger protec tion) when the terminal cover is mounted. weight approx. 100 g
1/32 din digital panel meter k3gn k-9 panel indicators characteristics note 1. the minimum input time for control signals is 80 ms. 2. refer to n102 operation manual for more details. input signal process voltage (1 to 5 v, 0 to 5 v, 5v, 10 v) process current (4 to 20 ma, 0 to 20 ma) no-voltage contact (30 hz max. with on/off pulse width of 16 ms min.) open collector (5 khz max. with on/off pulse width of 90 s min.) digital data display (by rs-485 communication) a/d conversion double integral method 14 bit resolution --- sampling period 250 ms --- display refresh period sampling period (sampling times multiplied by number of averaging times if average processing is selected.) pulse measurement method --- periodic measurement --- connectable sensors --- on residual voltage: 2.5 v max. off leakage current: 0.1 ma max. load current: must have a switching capacity of 15 ma min. must be able to reliably sw itch load currents of 5 ma max. max. displayed digits 5 digits ( ? 19999 to 99999) display 7-segment digital display, character height: 7.0 mm polarity display ? ? ? is displayed automatically with a negative input signal. zero display leading zeros are not displayed. scaling function programmable with front-panel key inputs (range of display: ? 19999 to 99999). the decimal point position can be set as desired. external controls (see note 1) hold: (measurement value held) zero: (forced-zero) --- hysteresis setting programmable with front-panel key inputs (0001 to 9999). other functions programmable color display selectable output operating action teaching set values average processing (simple average) lockout configuration communications writing control (c ommunications output models only) forced-zero set with front panel keys control inputs (hold/zero) selection via front panel keys field calibration startup compensation time (0.00 to 99.9 s) auto-zero time (0.0 to 19.9 s) output relays: 2 spst-no transistors: 3 npn open collector 3 pnp open collector combinations: communications output (rs-485) + relay outputs (2 spst-no); communications output (rs-485) + transi stor outputs (3 npn open collector); communications output (rs-485) + transistor outputs (3 pnp open collector) communications communications function: rs-485 delay in comparative outputs (transistor outputs) 750 ms max. degree of protection front panel:nema4x for indoor use (equivalent to ip66) rear case: iec standard ip20 terminals: iec standard ip20 memory protection non-volatile memory (eeprom) (possible to rewrite 100,000 times)
k-10 1/32 din digital panel meter k3gn measuring ranges process voltage/current inputs no-voltage contact/open collector inputs digital data display (by rs-485 communications) input/output ratings relay contact output (incorporating g6k relays) transistor output communications specifications refer to n102 operation manual for more details. input measuring range measuring accuracy input impedance displayable range dc voltage 1.000 to 5.000 v/ 0.000 to 5.000 v 0.1% fs 1 digit max. (at 23 3 c) 1 m ? min. ? 19999 to 99999 (with scaling function) ? 5.000 to 5.000 v 0.1% fs 1 digit max. (at 23 5 c) ? 10.00 to 10.00 v dc current 4.00 to 20.00 ma/ 0.00 to 20.00 ma 0.1% fs 1 digit max. (at 23 3 c) 60 ? input measuring range measuring accuracy (at 23 5 c) displayable range no-voltage contact (30 hz max.) with on/ off pulse width of 16 ms min. 0.05 to 30.00 hz 0.1% fs 1 digit max. ? 19999 to 99999 (with scaling function) open collector (5 khz max.) with on/off pulse width of 90 s min. 0 to 5000 hz displayable range ? 19999 to 99999 item resistive load (cos = 1) rated load 1 a at 30 vdc rated carry current 1 a max. (at com terminal) max. contact voltage 60 vdc max. contact current 1 a (at com terminal) max. switching capacity 30 va min. permissible load (p level, reference value) 10 mv, 10 a mechanical life 50,000,000 times min. (at a switching frequency of 36,000 times/hr) electrical life (at an ambient temperature of 23 c) 100,000 times min. (at the rated load with a switching frequency of 1,800 times/hr) rated load voltage 24 vdc max. load current 50 ma leakage current 100 a max. item rs-485 transmission method 2-wire, half-duplex synchronization method start-stop synchronization baud rate 1,200/2,400/4,800/9,600/19,200 bps transmission code ascii communications reading/writing to the k3gn read/write set values, read/write scaling values, enable/disable the writing of data through commu- nications, forced-zero control, and other data.
1/32 din digital panel meter k3gn k-11 panel indicators connections terminal arrangement note: *operation power supply 24vdc: recommended dc power supply: eg. omron s8vs terminal no. name description a - b operation power connect the operation power supply. c - b event input or pulse/contact input operates as follows depending on parameter setting:  holds process value.  calibrate the process value to zero and clear the forced-zero function.  pulse or contact input. c - a d , f - e analog input connect the voltage or current analog input. g - h communications rs-485 communications terminals. i , k - l outputs outputs relay or transistor outputs. there is also a pass output for models with transistor outputs. i , j , k - l b (+) a ( ? ) 78 7 8 c 12 3 1 2 3 a 9101112 9101112 9101112 d 456 b c d ab 78 9101112 123 456 output terminals input terminals nc nc rs-485 models with npn inputs models with pnp inputs out1 pass nc out2 com out1 out2 com out1 pass out2 com voltage current analog input com event or pulse/contact input event or pulse/contact input analog input models without communications models with communications operation power supply 24 vdc* operation power supply 24 vdc* models with pnp transistor outputs models with npn transistor outputs models with relay outputs
k-12 1/32 din digital panel meter k3gn wiring block diagram input circuits analog input (dc voltage/current) pulse input/control event input (hold/zero) display key drive circuit drive circuit drive circuit constant voltage circuit 1 power supply circuit input circuit operating power supply constant voltage circuit 2 eeprom analog input terminal pulse/ control input terminal control input circuit a/d conversion circuit waveform rectification circuit micro- computer note: 1. transistor output models only. 2. relay output models only. 3. models with communications functions only. output circuit communica- tions driver transistor output (see note 1.) contact output (see note 2.) communications terminal (see note 3.) 5 4 5 6 a 60 ? a+b=1 m ? b voltage input com current input com to a / d to a/d 2 3 24 vdc + 4.7 k ? 2.35 k ? 3 4.7 k ? 2.35 k ? 2 24 vdc ? 24 vdc + 24 vdc ? 1 1 pnp input npn input hold/zero pulse hold/zero pulse
1/32 din digital panel meter k3gn k-13 panel indicators output circuits contact output transistor output 9 11 12 5 v 5 v out1 out2 out3 9 10 11 12 8.2 ? 8.2 ? 8.2 ? out1 out2 pa s s com npn output 9 10 11 12 8.2 ? 8.2 ? 8.2 ? out1 out2 pa s s com pnp output
k-14 1/32 din digital panel meter k3gn operation main functions input types and ranges scaling analog (process) inputs the k3gn converts input signal s into desired physical values. input2: any input value display2: displayed value corresponding to input2 input1: any input value display1: displayed value corresponding to input1 pulse frequency the k3gn converts pulse signal inputs into desired units such as revolutions or rotational speeds. the slope of the linear relation ship between the input value and dis- play value is calculated automatically when an input value and its corresponding display value are entered. input value: any arbitrary input value display value: desired display va lue corresponding to input value if scaling for pulse signals is no t performed, the input frequency will be displayed. the relationship between input, f, and display, d, is expressed in the form d = f a (multiplication factor). the value of a will vary accord- ing to the display unit. for example, if the display unit is rpm, y is given by the following: d = f 1/n 60 (i.e., a = 1/n 60) where n is the number of pulses per revolution and f is the input pulse frequency (hz). if the display unit is m/min, y is given by the following: d = f d 1/n 60 (i.e., a = d 1/n 60) where d = the wavelength (m) per revolution. example : when displaying the rotational speed (rpm) for a machine that generates 5 pulse signals per revolution, d is given by the follow- ing: d = f 1/5 60, so if f = 1, then d = 12. therefore, input 1 for inp and 12 for dsp . average processing the average processing function stabil izes displayed values by aver- aging the corresponding input signal s that fluctuate dynamically. hysteresis the hysteresis of comparative outputs can be set to prevent the chat- tering of relay or transistor outputs. input type (setting parameter) function input range (setting parameters) setting range analog input ( analg ) selects dc voltage/current signal input. 4 to 20 ma/0 to 20 ma ( 4-20 ) displayable from ? 19999 to 99999 with scaling function. the position of the decimal point can be set as desired. 1 to 5 v/0 to 5 v ( 1-5 ) 5 v ( 5 ) 10 v ( 10 ) pulse input ( pulse ) selects pulse input signal. 0.05 to 30 hz ( 30 ) 0 to 5 khz ( sk ) remote ( rmt ) displays digital data from plc or pc. --- input value input1 input2 input value displayed value displayed value display1 display2 display1 display2 input2 input1 inp dsp input value displayed value k3gn proximity sensor upper limit (high acting) set value output on off hysteresis measurement value
1/32 din digital panel meter k3gn k-15 panel indicators startup compensation time (pulse input only) the startup compensation time par ameter keeps the measurement operation from sending an unnecessa ry output corresponding to instantaneous, fluctuating input from the moment the k3gn is turned on until the end of the preset period. the compensation time can be set in a range from 0.0 to 99.9 sec- onds as the waiting time until t he devices subject to measurement become stable after the startup of the power supply. changing the display color the display can be programmed to change color when an output turns on. in an example, the k3gn can be programmed to display green for normal, and red for errors. the color can be set to change from either green to red or red to green when output turns on. k3gn can also be programmed to display only one unchanging color: red or green. teaching an actual measured value as a set value without any front panel key input can be set with the teaching f unction. teaching is useful for making settings while checking the operation status of k3gn. forced-zero function it is possible to shift the zero point to a desired value (such as might be required when adjusting reference values) with one touch of the up/zero key on the front panel. configurable output operating action output 1 and output 2 can be set to operate in one of the 3 following modes:  upper limit (high acting): the output is turned on when the measured value is greater than its set value.  lower limit (low acting): the output is turned on when the measured value is less than its set value.  upper and lower limits (outside band acting): an upper limit (h set value) and lower li mit (l set value) can be set independently. the output is turned on when the measured value is greater t han upper-limit set value or less than the lower-limit set value. only transistor outputs have a pass output which is output when both out1 and out2 are off. the three types of output operations shown above can be combined as desired. the following are ex amples of possible combination s. out1 out2 sv zero hold cmw upper limit (high acting) out1/2 set value measurement value on off output hysteresis lower limit (low acting) out1/2 set value on off output hysteresis hysteresis measurement value hysteresis on off output measurement value upper and lower limits (outside band acting) upper-limit set value for out1/2 lower-limit set value for out1/2 upper limit 2-stage output threshold output on off out2 on off out1 out1 set value on off out2 on off out1 on off out2 on off out1 out2 set value out1 set value measurement value upper-limit out2 set value upper-limit out1 set value lower-limit out1 set value lower-limit out2 set value measurement value combination of upper limit and upper/lower limits upper-limit out2 set value lower-limit out2 set value measurement value
k-16 1/32 din digital panel meter k3gn nomenclature name functions 1. main display displays process values, parameters, and set values. 2. status indicators out1 lit when output 1 is on. out2 lit when output 2 is on. sv lit when a set value is being displayed or changed. t lit when the teaching function is enabled. flas hes when the k3gn is in teaching operation. lit when a calibration value is being displayed during user calibration. flashes while reading a calibra- tion value. zero lit while the forced-zero function is activated. hold lit when hold input is on. cmw lit when communications writing is ?enabl ed? and is out when it is ?disabled.? 3. level indicator displays the current level that the k3gn is in. (see below for details.) 4. level key used to change the level. 5. mode key used to allow the main display to indicate parameters sequentially. 6. shift key used to enable that set value to be changed. when changing a set value, this key is used to move along the digits. 7. up/zero key used to change a set value. used to set or clear a forced-zero function when a measurement value is being displayed. 1. main display 2. status indicators 3. level indicator 4. level key 2. status indicators 7. up/zero key 6. shift key 5. mode key level indicator level p protect not lit operation a adjustment s initial setting c communications setting f advanced function setting u user calibration
1/32 din digital panel meter k3gn k-17 panel indicators dimensions note: all units are in millimeter s unless otherwise indicated. application examples detection of dust exhaust the change in the density of the dust is detected via the e3sa and discriminated by the k3gn. monitoring of tank pressure the output of the pressure sensor is processed and the pressure is displayed. remote monitoring of the operation is possible with the communications function. 22.2 +0.3 0 22.2 +0.3 0 45 +0.6 0 3.6 mm 7 mm main display character size panel cutouts gang mounting (48 no. of panels ? 2.5) +1.0 0 40 min. separate mounting the products cannot be made waterproof when gang-mounted. the k3gn uses m3 terminals. a terminal cover is provided. exhaust grinder dust collecting machine e3sa 4 to 20 ma k3gn out2 (upper upper- limit alarm) device stops out1 (upper-limit alarm) output reduction instruction foam beer tank exhaust valve pump k3gn host pc rs-485 rs-232c e8aa pressure sensor
k-18 1/32 din digital panel meter k3gn monitoring of motor load current if the startup time compensation of the k3gn is enabled, the k3gn will not be influenced by the inrush current from starting the motor, and no signal will be output from the k3gn. note: *power supply: recommended dc power supply: eg. omron s8vs. monitoring difference between two line speeds the difference between the two line speeds is calculated by the plc and the result is written via rs-485 to the k3gn where it is dis- played. position indication on x-y table the position on the x-y table is calculated by the plc and the result is written via rs-485 to the k3gn where it is displayed. the scaling function can be used to display the result in millimeter units. monitoring the rema ining quantity of soup the distance to the surface of the soup is detected with an ultrasonic sensor and, based on this distance, the k3gn displays the remaining quantity. when the remaining quantity of soup decreases to less than 20%, the k3gn lights the ?replenish? indicator. monitoring number of motor revolutions note: *power supply: recommended dc power supply: eg. omron s8vs. power supply* signal input k3gn 24-vdc power supply* electroma- gnetic relay k3fk ct converter out1 (upper-limit alarm) out2 (lower-limit alarm) rs-485 communications output (calculation result) k3gn (set the in- put type to "remote"). x y plc mm mm 00 135.4 plc x-y table rs-485 communica- tion output k3gn (set the in- put type to "remote".) 100 % 20 % 4 to 20 ma k3gn volume of soup out 1 replenish e4pa-ls50-m1 ultrasonic sensor large cup medium cup small cup power supply* signal input 24-vdc power supply* electromagnetic relay 0 to 1 a 4 to 20 ma k3fk ct converter k3gn-ndc k3gn-ndc out1 (upper limit) out1 (upper limit) out2 (lower limit) out2 (lower limit) e2e proximity sensor
1/32 din digital panel meter k3gn k-19 panel indicators precautions !warning do not touch any of the termi nals while power is being supplied. doing so may result in electric shock. also, do not touch the termi- nals with a screwdriver while pow er is being suppl ied. electrical shock may result via the screwdriver. !caution do not allow metal objects or conductive wire cuttings to enter the product. doing so may result in elec tric shock, fire , or malfunction. !caution do not attempt to disassemble, repair, or alter the product. doing so may result in electric shock, fire, or malfunction. !caution do not use the product where fl ammable or combustion gasses are present. !caution the lifetime of output relays varies greatly with the switching ca- pacity and conditions. consider the actual operating conditions, and use the product within the rated load and electrical service life. !caution do not use loads exceeding the rated value. doing so may result in damage or burning. !caution use a power supply voltage within the specified ratings. not doing so may result in damage or burning. !caution be sure to tighten the terminal screws securely. the recommend- ed tightening torque is 0.5 nm. loose screws may result in prod- uct failure or malfunction. !caution perform correct setting of the pr oduct according to the application. failure to do so may cause unexpected operation, resulting in damage to the unit or injury. !caution this product is not a safety devic e. product failure may prevent op- eration of comparative outputs. take safety measures, such as in- stalling a separate monitoring system, to ensure safety and to prevent serious accidents caused by such failure, thus ensuring safety. observe the following precautions to ensure safety: 1. do not connect anything to unused terminals. 2. be sure to check each terminal for correct number and polarity before connection. incorrect or reverse connection may damage or burn out internal components of the k3gn. 3. do not use the product in locations subject to the following:  dust or explosive gasses (e.g., sulfide gas or ammonia gas).  condensation or icing as a result of high humidity.  outdoors or in direct sunlight.  splashing liquid or oil atmosphere.  direct radiant heat from heating equipment.  extreme changes in temperature. 4. do not block heat dissipation around the product, i.e., provide suf- ficient space for heat dissipation. do not block the ventilation holes on the back of the product. 5. do not use paint thinner for cleaning. use commercially available alcohol. 6. use a power supply meeting the po wer supply specifications of the k3gn. be sure that the rated voltage is achieved within 2 s after turning on the power. 7. use the k3gn within the specified temperature and humidity ranges. when installing the k3gn in a panel, be sure that the temperature around the k3gn (not the temperature around the panel) does not exceed 55 c. if the k3gn is subject to radiant heat, be sure that the temperature of the surface of the k3gn exposed to the radiant heat does not exceed 55 c by providing a fan or other heat removal method. 8. store the k3gn within the specified temperature and humidity ranges. 9. do not lay heavy objects on the product during use or storage. doing so may deform or deteriorate the k3gn. 10. conduct aging for 15 minutes min. after power is on for correct measurement. mounting recommended panel thickness is 1 to 5 mm. insert the k3gn in the square cutout, insert the adapter from the back, and push the k3gn into the cutout as far as possible. use screws to secure the k3gn. to make the k3gn waterproof, insert watertight packing in the k3gn. install the watertight packing in the proper direction. note that the packing is direction-sensitive. when gang-mounting two or more products in a cutout, be sure that the ambient temperature does not exceed the specifications. mount the k3gn as horizontally as possible. separate the k3gn from machines generating high-frequency noise, such as high-frequency welding machines and high-frequency sew- ing machines. operation a k3gn model with a relay contact or transistor output may not out- put any alarm signal normally if the model has an error. it is recom- mended that an independent alarm device be connected to the model. the parameters are factory-set so that the k3gn will operate nor- mally. the settings of the parameters may be changed according to the application. wiring wire the power supply with the corr ect polarity. wiring with incorrect polarity may result in damage or burning. wire the terminals using crimp terminals. tighten terminal screws to a torque of approx. 0.5 nm. wire signal lines and power lines s eparately to reduce the influence of noise. use m3 crimp terminals of the type shown below. 5.8 mm max. 5.8 mm max.
k-20 1/32 din digital panel meter k3gn operating procedures initial settings specify set value of out 1 and 2. measurement starts. power on press the level key @ for 3 s min. to move to the initial setting level. select the input type and specify the analog input range or pulse frequency input range. set the scaling values and specify output operating action as required. with communications output models, press the level key @ for less than 1 s to move to the communications setting level. after making communications settings, press the level key @ for less than 1 s to move to the initial setting level. move to the advanced function setting level and make settings for average processing, hold/zero selection, hysteresis val- ues, auto-zero time, startup compensation time, display color programming, and other advanced function parameters as re- quired. press the level key @ for less than 1 s min. to return to the operation level.
1/32 din digital panel meter k3gn k-21 panel indicators levels ?level? refers to a grouping of parameters. the following table lists the operations that are possible in each of the levels, a nd how to move between levels. there are some parameters that are not displayed for certain models. note: the move to protection level time can be set in the advanced function setting level. level name function measurement protect setting lockouts. continue operation displaying process values, se tting/clearing forced-zero function, and setting out 1/2 set values. continue adjustment setting communications writing control. continue initial setting making initial settings of input type, scaling, output operating action, and other parameters. stopped communications setting setting baud rate, word l ength, and other communications data. stopped advanced function setting setting average processing, display color settings, and other ad- vanced function parameters. stopped calibration setting user calibration of the inputs. stopped + + -1234.5 protection operation adjustment power on 1 s min. 1 s min. initial setting password " ? 0169" 1 s min. calibration password "1201" continue to press the key for 2 s min. indicates change of level. 1 s min. less than 1 s less than 1 s (see note) time set by user flashing stops if key is released. communications setting advanced function setting
k-22 1/32 din digital panel meter k3gn parameters ? ? ? ? ? ? ? adjustment level press level key for less than 1 s. power on operation level set one of these. set one of these. process value note: 1. some parameters are not displayed for certain models. 2. the k3gn will stop measurement if the level is changed to the initial setting level, the advanced function setting level, the communications setting level, or the calibration level. 3. if the input range is changed, some parameters are set to default values. therefore, set the input range first. 4. settings displayed in reverse black/white are defaults. commu- nications writing control out1 set value upper-limit out1 set value lower-limit out1 set value out2 set value upper-limit out2 set value lower-limit out2 set value monitor status setting status next parameter the set value flashes. if there is no key op- eration for 5 seconds, the setting is regis- tered and the display returns to monitor sta- tus. change the set value using the up key and the shift key . changing set values while parameters are being displayed, set values can be displayed by pressing the shift key (monitor status). pressing the shift key again will make it possible for this set value to be changed (setting status). the part that can be changed will flash. change the set value as required, and press the mode key to reg- ister the setting and move to the next parameter.
1/32 din digital panel meter k3gn k-23 panel indicators ? ? ? ? ? ? ? ? ? press level key for less than 1 s. for analog input for pulse input for pulse input press level key for more than 1 s. enter password " ? 0169" unit: times unit: s unit: s unit: s unit: ms for pulse input input type analog pulse baud rate stop bits parity bits none even odd initial setting level green (red) green red (green) red unit: hz upper limit lower limit upper limit lower limit unit: s for analog input enter password "1201" calibration level communications setting level commu- nications unit no. word length press level key for more than 3 s. press level key for more than 1 s. remote (digital data display) analog input range input-pulse frequency range for analog/ remote input input value 1 for scaling display value 1 for scaling input value 2 for scaling display value 2 for scaling input value for scaling display value for scaling decimal point position operating action for out1 set value operating action for out2 set value move to advanced function setting level upper/lower limits upper/lower limits move to calibration level send waiting time move-to- protect- level time display auto-return time display color change startup compen- sation time auto-zero time out2 hysteresis out1 hysteresis for analog/ remote input hold/ zero selection average processing parameter initialization advanced function setting level ? ? ? ? ? ? ? ? ? ? ? ? ? ? ?
k-24 1/32 din digital panel meter k3gn operation/adjustment lockouts prohibits key operations for operation level and adjustment level.  initial setting is 0.  when the set value is 0 (the initia l setting), protection is not set. setting change lockout prohibits setting changes.  the initial setting is off. note: changes to protection level parameters, moving to advanced function setting level, and moving to calibration level are all al- lowed. initial setting/communications lockouts prohibits moving to the initial se tting level, the communications set- ting level, and the advanced function setting level.  the initial setting is 1. forced-zero shift lockout prohibits the setting or clearing of a forced-zero using the front panel key.  the initial setting is off. p p p p protect level setting change lockout ? prohibits setting changes using front panel keys. operation/adjustment lockouts initial setting/communi- cations lockouts forced-zero shift lockout ? prohibits menu display, writing, etc., for operation level and adjustment level. ? prohibits access to menu display, initial setting level, communications setting level, and advanced function setting level. ? prohibits use of the forced-zero function using front panel keys. setting operation level moving to adjustment level process value display set value display 0 allowed allowed allowed 1 allowed allowed prohibited 2 allowed prohibited prohibited setting meaning off setting changes using front panel keys allowed (i.e., it is possible to move to the st ate where changes to settings can be made). on setting changes using front panel keys prohibited (i.e., it is not possible to move to the state where changes to settings can be made). setting moving to initial setting level moving to communications setting level 0 allowed (message for mov- ing to advanced function setting level displayed) allowed 1 allowed (message for mov- ing to advanced function setting level not displayed) allowed 2 prohibited prohibited setting meaning off executing and clearing of forced-zero allowed. on executing and clearing of forced-zero prohibited.
1/32 din digital panel meter k3gn k-25 panel indicators troubleshooting when an error occurs, error details will be di splayed on the main display. confirm the error from the main display and take the appropriate coun- termeasures. main display level display error contents countermeasure e111 (e111) not lit ram memory error turn the power supply off and on again. if the same error is displayed even after the power is turned off and on, it is necessary to replace the memory. if normal operation is restored by turning the power supply off and on, it is possible that ther e is noise interference. check that there is nothing in the vicinity that may be the source of noise. e111 (e111) 5 eeprom memory error s.err (s.err) (flashes at 0.5-s intervals) not lit input error or input range exceeded all outputs turn off. check for incorrect input wiring, fo r disconnected power lines, for short- circuiting, and the input type. bring the input value within range. 99999 (flashes at 0.5-s intervals) not lit greater than displayable range this is not an operational error. these messages are displayed when a value to be displayed lies outside the displayable range, even if the input value is within the input range and the range for which measurement is possible. bring the input value and display value within range. -19999 (flashes at 0.5-s intervals) not lit less than displayable range
k-26 1/32 din digital panel meter k3gn additional information application as a process meter the initial settings required when using the k3gn a proc ess meter are explained below using the following example. setting example inputs in the range 1 to 5 v are scaled to the range 0 to 100.0 kg and displayed. if the measurement value goes over 70.0 kg, output 1 turns on. if the measurement value goes below 50.0 kg, output 2 turns on. initial setting procedure 1. check the wiring and turn on the power. 2. set analog input as the input type. if a measurement value is display ed (operation level), move to the initial setting level by holding down the level key for 3 s min. set parameter in-t to analg . 3. set the analog range to 1 to 5 v. set parameter range to 1-5 . 4. set the scaling values. set parameter inp.1 to 1.000 . set parameter dsp.1 to 0 . set parameter inp.2 to 5.000 . set parameter dsp.2 to 1000 . 5. set the position of the decimal point. set parameter dp to %%%%.% . 6. operating action for out1 and out2 set values. set parameter out1.t to hi . set parameter out2.t to lo . 7. set out1 set value to 70.0 and out2 set value to 50.0. if an initial setting level parameter is displayed, press the level key for 1 s min. to return to the operation level. set parameter out1 to 70.0 . set parameter out2 to 50.0 . 8. start actual operation. application as a tachometer the initial settings required when using the k3gn as a ta chometer are explained below using the following example. setting example the speed of a conveyor belt is displayed in m/min units. for every revolution of the shaft, 4 pulses ar e output. the diameter of the axis of rotation is 12 cm. if the rota tional speed goes over 10.500 m/min, output 1 turns on. if the speed goes below 9.500 m/min, output 2 turns on. deciding the scaling value rotational speed (m/min) = diameter (m) revolutions per minute (rpm) revolutions per minute (rpm) = input frequency (hz) number of pulses per revolution 60 applying the appropriate values to these 2 equations gives: speed (m/min) = 5.654866... input frequency (hz) multiply by 1,000 to display the firs t 3 digits to the right of the decimal point. speed (m/min) = 5654.866... input frequency (hz) 100.0 kg 0.0 kg 1.000 v 5.000 v 50.0 kg 70.0 kg input value output 2 output 1 normal displayed value 12 cm output 1 9.500 m/min 10.500 m/min normal output 2 56549 10 hz input value displayed value to limit inaccuracies due to scaling, select a round number (e.g., 10) as the input value and select a display value of as many digits as possible. in this example, scaling is performed so that an input value of 10 gives a displayed value of 56549.
1/32 din digital panel meter k3gn k-27 panel indicators initial setting procedure 1. check the wiring and turn on the power. 2. set pulse input as the input type. if a measurement value is displayed (operation level), move to the initial setting level by holding down the level key for 3 s min. set parameter in-t to pulse . 3. set the pulse frequency to 30 hz. the input pulse frequency for t he application is approximately 2 hz and so can be assumed not to exceed 30 hz. set parameter p-fre to 30 . 4. set the scaling values. set parameter inp to 10 . set parameter dsp to 56549 . 5. set the decimal point. set parameter dp to %%.%%% . 6. operating action for out1 and out2 set values. set parameter out1.t to hi . set parameter out2.t to lo . 7. set out1 set value to 10.500 and out2 set value to 9.500. if an initial setting level parameter is displayed, press the level key for 1 s min. to return to the operation level. set parameter out1 to 10.500 . set parameter out2 to 9.500 . 8. start actual operation.
k-28 1/32 din digital panel meter k3gn in the interest of product improvement, specif ications are subject to change without notice. all dimensions shown are in millimeters. to convert millimeters into inches, multiply by 0.03 937. to convert grams into ounces, multiply by 0.03527. cat. no. n101-e1-03


▲Up To Search▲   

 
Price & Availability of K3GNNDT2FLK24VDC

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X